|
Approach Locking Circuits This page explains the circuits used to provide approach and back locking in 1950s era individual function switch panels. Signal 74 at Petone is used as an example. |
|
|
Diagram Normal Lock Relay Lockstick & Reverse Lock Relay Signal Lighting |
|
Track Diagram
![]() |
|
Locking Relays. Associated with each lever on the panel are a Normal locking relay and a Reverse locking relay. Only one of these relays can be energised at a time. It is possible for both to be de-energised. |
Signal Normal Lock Relay. This relay must be up for associated interlocking to be free. Signal Approach and Back locking is implemented by preventing the Normal Lock Relay from picking. 44 and 38 points both require 74 normal. |
Normal Lock Relay
![]() |
|
Freeing the interlocking. The normal lock relay 74NLR must be up for the interlocking to be released. Approach and back locking works by preventing 74NLR from picking. |
JR. If lock stick is up (train has not passed signal), approach circuit 77T is occupied and the lever put back to normal (74RLR down) 60 second timer JR will operate. When JR has run down it bypasses the approach locking circuits. |
Lock Stick And Reverse Lock Relay
![]() |
|
Lock Stick. If the signal is normal (74NLR up) and the track in advance is not occupied (44TPR up) the lock stick will operate and stick on its own front contact (74LS). |
Reverse Lock Relay. 74RLR requires that either the lever on the panel be Reverse or that the down main be switched out (2RLR). In addition 74RLR will only pick if points are in the correct position. |
Lighting
![]() |
|
Signal Lighting. If the signal is reverse (7RLR up), the lock stick (74LS) is up and the timer (74JR) is not operating the signal can show a proceed indication. The actual indication shown is determined by the position of 44 points and the state of the track circuits. |
Flasher. If 74 signal is at stop (74RGPR), 74LS is down and the lever is not Normal the red light will be operated by 1DFR which is a flasher. This indicates that the lever is out of correspondance and should be put back to normal. If the lock stick (74LS) is up the flasher will be bypassed and the red light will not flash when the lever is reversed. |
Last Updated: Sun Apr 22 10:34:12 NZST 2012